  1. Digger556

    I guess it's a LPW2, not a DN2M...

    I thought it was curious. All my other units have "Onan" casted into the valve covers. I was surprised to see it branded Lister, even though it is. When did production of the 802 and 803s end? Maybe they ran short of Onan branded parts and said screw it, and finished production with Lister...
  2. Digger556

    MEP Generator Output Waveforms and THD

    3600 rpm, open frame, box store generators are all terrible. This was a Honda-built unit I tested. I doubt off-brand is better.
  3. Digger556

    I guess it's a LPW2, not a DN2M...

    Popped the top on my newest auction win and found something out of the ordinary. Mid-2011 build
  4. Digger556

    MEP Generator Output Waveforms and THD

    Just do it. :LOL:
  5. Digger556

    Irish Spring soap (Rodent Deterrent)

    Back in the day, I built large parade floats. The artistic parts were made of fabric foam, cloth, and spray foam. The mice loved that stuff for nest building. We used dryer sheets to keep them away and never had a problem afterwards. I never understood the sciemce behind it, but it did work...
  6. Digger556

    MEP Generator Output Waveforms and THD

    My local utility power was more distorted than what my 802a was producing. I consider the TQGs to be "clean" power.
  7. Digger556

    MEP Generator Output Waveforms and THD

    Okay, I can do that with mine. Thanks!
  8. Digger556

    MEP Generator Output Waveforms and THD

    How did you calculate THD with that scope? I have a Rigol DS1054Z and I think the only good way to do it is export the raw data.
  9. Digger556

    MEP Generator Output Waveforms and THD

    Thanks for the data points! I've been wanting to revisit this and quantify the THD, so you are saving me a lot of effort. Here a comparison to some other generators and inverters I did previously: https://www.steelsoldiers.com/threads/mep-802a-power-quality-with-oscilloscope-pics.190724/
  10. Digger556

    MEP802A overload tripping

    If you have everything wired up correctly and it trips the overload after a min or so, it is likely the contacts in S6 or S8 are dirty. Buy a spray can of Deoxit D5 and thoroughly clean out those 2 switches to start with.
  11. Digger556

    Is there a treaded barbed fitting for the oil drain on the mep802?

    1/2 NPT to barb fitting. Available at any hardware store.
  12. Digger556

    MEP 803A in 1/2 ton pickup truck bed ?

    It will fit and payload will be fine. The loader will need longer than std forks or you should remove your tailgate for loading. How you planning to get it out?
  13. Digger556

    First MEP 803A, fix up help

    8 for a 802a 4 for a 803a When looking at the CT, remember there are multiple conductors. I think it was 2 each.
  14. Digger556

    20kw Generator

    All true, but this requires equipment to have 3-phase motors and most residential A/Cs have single phase motors. You could swap the condensor fan easily, but the compressor is still single phase. Newer, high SEER, A/Cs are already inverter driven. (Which is great)
  15. Digger556

    20kw Generator

  16. Digger556

    20kw Generator

    18-20 kW inrush would be consistent with an older 3.5 - 4 ton A/C unit. Locked Rotor Amps (LRA) on startup would be around 80 amps and running wattage would be 4 kW-4.5 kW. That would be equivilent to a 4hp air compressor. To put this in perspective, here is a video of a 10 kW, MEP-803a...
  17. Digger556

    20kw Generator

    Do you really need 20kW for a house? Are you all electric? A 10 kW unit will run most houses with A/C. For those with high efficiency A/C's, like me, you can run the whole house on a 5 kW unit. You can't just say "I want the big one to run everything" because all mil sets are diesel and you...
  18. Digger556

    What is wrong me me.. Another MEP803...

    Picked up an 802a today and asked my load out guy about the computer upgrade. He confirmed everthing that was left (in his mostly empty lot) was sold and waiting for pickup. Starting next week, his delivery guy is telling him to expect 10 truck loads PER DAY! All the equipment is backed up on...
  19. Digger556

    What is wrong me me.. Another MEP803...

    Nice! Can't help you with addiction problems, cause I can't see a problem.:LOL: We dont have any nice units on trailers show up around here. I would like to find a decent camo M116A3
  20. Digger556

    803a sustained load in high heat.

    There is a data plate that lists temps and altitude ratings for these machines. On #2 diesel, 10kW @ 120 degrees at sea level,
Top