    MEP-831A will not start air compressor

    In general motor driven items draw about 4X the nameplate current at startup until they get up to speed. That high startup current is what's tripping the 831.
  2. K

    MEP-804A Smoke, what is the cause?

    Injection Pump
  3. K

    24 Volt Control Voltage. I have it here but not over there!

    MajorGasAttak - For starters, what model of generator are you working on? Do you have a copy of the relevant TM with the schematics in it?
  4. K

    MEP-804A Coolant Temperature Sender Part Number

    You can use Parttarget.com to get all the PNs for or a given NSN or PN. Put in 5905-01-392-8825 and you'll be get: 126864 06555 Beede Electrical Instrument Co. Inc. A A 88-22322 30554 Department of Defense Project A A 02094-00 1NBV2 Maxima Technologies A F 02094-00 16476 Maxima...
  5. K

    MEP-805A T1 Issue

    He's all set.
  6. K

    MEP-831a Inverter Overhaul

    I tested the diodes on both of my diode boards with my Fluke. *All diodes measured about .45V and infinity (after the caps charged from my meter) * Actually I found one of my diodes shorted.
  7. K

    MEP-831a Inverter Overhaul

    Not fixing it. It's one of several dead inverters I have laying around here. I use it for pictures only. The charring is from a trace that vaporized. It was the Load signal from the inverter going to the Governor Controller module. IC's are ON Semiconductor.
  8. K

    MEP-831a Inverter Overhaul

    Could be why so many of the inverters fail.
  9. K

    MEP-831a Inverter Overhaul

    Peter, Here are front and back pics of the same part on the top board. Ref Des on the PCB for it is C19 No marking on the back
  10. K

    MEP-831a Inverter Overhaul

    Peter, No inrush limiter. DC goes from diode bridge directly to the electrolytics. Only other parts on the assembly besides the two disc caps are a couple of caps between the power transistors and two bleeder resisters. I suspect it doesn't need a limiter since the PMA voltage rises as the...
  11. K

    MEP-831a Inverter Overhaul

    I'll tear my inverter down more and see if there is an inrush limiter.
  12. K

    MEP-831a Inverter Overhaul

    Here's a picture of one.
  13. K

    MEP-831a Inverter Overhaul

    Interesting. I've torn apart dead inverters and never saw one with a toasted disc capacitor. The 12 semiconductors on the left and right are diodes. They comprise the AC to DC rectification of the 3 phase AC power from the PMA.
  14. K

    MEP-831a Inverter Overhaul

    Correct
  15. K

    MEP-831a Inverter Overhaul

    831 haters :ROFLMAO: When they work they are great. Perfect 60 Hz output frequency & AC power plus stable VAC output. No droop like 802's and 803's. When the inverter fails it sometimes burns out one or more of the fuses. Check each of these 8 fuses by the PMA power input connectors to be...
  16. K

    MEP-831a Inverter Overhaul

    Part 2... Remove this bolt and spacer. (mine is missing it) Remove the screws attaching the fan and bottom panel. There are spacers where the bolt passes thru the fan housing. Pull the fan and base panel away. The bracket shown in the pic attached to the base panel would be loose by...
  17. K

    MEP-831a Inverter Overhaul

    Here is how to get the jig saw puzzle apart :) This will be two posts since only 10 pictures allowed per post. Take the top and two large side panels off. Unplug the three black connectors Remove the three nuts and bolts attaching the control board to the frame (mine is missing the middle...
  18. K

    MEP-831a Inverter Overhaul

    Yes, It is a bit confusing on how to get the unit apart to service those capacitors. I'll shoot some pictures for you on the step by step to get it apart and post them up here. I've disassembled them numerous times!
  19. K

    MEP-803a voltage drop during monthly test

    Yes, the higher than voltage range is there so that users can use the generator to power applications that require higher voltage than the nominal 120/240/208. Had received several requests early on for that specific capability. This can be done as long as one doesn't exceed the overvoltage...
  20. K

    MEP-1030 Mouse Proofing & MEP-10XX WiFi Remote Start

    Inquiring minds... Yes I am :) The design is very similar in architecture and features as my 80X systems. Hundreds of those in use across the US, it's territories and foreign countries. The new Remote Starts will support all the MEP-10XX sets. FEATURES - 2-Wire Start/Stop of course, plus...
Top
AdBlock Detected

We get it, advertisements are annoying!

Sure, ad-blocking software does a great job at blocking ads, but it also blocks useful features of our website like our supporting vendors. Their ads help keep Steel Soldiers going. Please consider disabling your ad blockers for the site. Thanks!

I've Disabled AdBlock
No Thanks