Also make sure the generator is adjusted to the correct AC output voltage. If it's not correct the AC may draw more current and for longer than usual at startup.
You might try generatorguru.com
I've used them before to get parts for repairing consumer generators.
They do list a number of Northstar Generators and list parts for them including power connectors like the one you are looking for.
They had an interesting hint on their website regarding...
The specifications for operation of the overload in the set are as follows:
0% to 110% Load on any leg of the generator will Not trip an overload
130% Load on any leg of the generator will trip an overload in 8 +/-2 minutes
The overload detector operates on an inverse time principal. This...
Correct. It will NOT produce power unless the voltage selection door on the Inverter is fully closed.
There is a microswitch inside the inverter cover to sense if that little door is closed.
If you are running two 12 volt batteries in series it's best to use two 12 volt chargers instead of a single 24 volt charger. That way the two batteries are kept balanced.
I have two Battery Tender 12V 750mA wall wart chargers that I can let go cheap. Not using them anymore. I switched to a...
If you do have a meter you'll want to connect the meters negative lead to chassis ground and the positive lead to S5-5.
Start the generator.
1) You should measure ~24 volts DC there. Do you get that reading?
2) Then lift and hold S5 UP. The voltage at S5-5 should now be ~ 0 volts DC. Do you...
If you find the problem IS the switch then....
A potential replacement candidate for the 8906K4519 S5 Interruptor switch is a Honeywell 2TL1-70. They are about $39.
The contact operation of the 2TL1-70 is slightly different than the 8906K4519 so some wires would go to different terminals.
I...
When you lift the switch UP and hold it up does the green contactor light illuminate?
Does it then go out when you release the switch?
These switch's seldom go bad so I'd suspect the issue with the contactor not closing is due to something else.
There are two diode assemblies in the gen head.
5961-01-019-8003 Onan PN 358-0070 Can be found on ebay
and
5961-01-021-2232 Onan PN 358-0069 Can be found on ebay
My suspicion is that moisture gets into the unsealed potentiometers on the main control board inside the inverter causing their resistance values to change. The potentiometers are there so that the manufacturer can adjust parameters such as the Short Circuit threshold and a number of other trip...
MEP-804A, MEP-804B, MEP-805A, MEP-806A Replacement A1 AC Voltage Regulator
Posted this in the wrong section. See my my listing in the Classifieds for info.
See link in signature
The Remote Start systems are now available for the MEP-804A, MEP-804B, MEP-805A & MEP-806A generators!
See link in my signature to navigate to the listings.
Earlier in the manual in 3-12 it does call out "Tighten injector pipe nut (2) to 21 ft-lbs (28.5 Nm)."
It would look like 21 ft-lbs is the correct value.
Need to do one more test in an 804 before calling it good.
The %Load measurement was a bit off and want to get that solid before releasing it.
Wife had a medical issue recently and that took priority. All better now.
Good news is it will support the MEP-804A, MEP-804B, MEP805A & MEP-806A.