Search results

  1. Scoobyshep

    Need some GETT / Applied ECU / 23kw 3 Phase Generator Electrical Help

    if it is relying on residual magnetism ( again I have never touched this specific unit) you may be able to flash it to get it going. had this happen to a generator at work, fresh rewind, it didnt have enough magnetism to get the reaction going. My boss thought i was crazy for requesting a...
  2. Scoobyshep

    Need some GETT / Applied ECU / 23kw 3 Phase Generator Electrical Help

    Looks like theres 2 excitation windings yellow blue and red red start wiyh the yellow blue pair and see if theres ever power on startup there. If its just a flash circuit it may only be present for a brief amount of time. I would alos check winding continuity. disconnect from the...
  3. Scoobyshep

    Need some GETT / Applied ECU / 23kw 3 Phase Generator Electrical Help

    Good afternoon, sounds like you have the operating manual might need to find the maintenance manual. I have never worked on this specific unit but I can offer some basic things to look at. First is field. If the head isnt getting excitatition it wont produce power. I would look there...
  4. Scoobyshep

    MEP-003A Replacement AC Voltage Regulator

    there may be an off the shelf option, I did something similar for a 005
  5. Scoobyshep

    MEP-003a AC voltmeter Frequency meter Digital replacement?

    Very low tech, very reliable and fun to stare at
  6. Scoobyshep

    MEP-003a AC voltmeter Frequency meter Digital replacement?

    I had to replace the frequency meter on my 003 and because I think they are cool looking and I was unsupervised it got a reed style meter
  7. Scoobyshep

    MEP-003a AC voltmeter Frequency meter Digital replacement?

    It should be line voltage. the Voltmeter (M5) is powered from generator output through switch S8 See TM 5-6115-585-12 page 53 for the diagram. if you dont have the TMs look up on the website header click the TM button and look for the post on mep003. Heres a very distinct possibility...
  8. Scoobyshep

    Help I got MEP-itis... It all started with just one

    Difference being, AA supports you in your quest to quit drinking, here we would encourage one another to buy another MEP
  9. Scoobyshep

    MEP-802A Popping CB1 as Soon as the Unit is Switched to Pump/Prime

    are you sure the CB is good? It's rare but I have had it happen before. Fast and dirty test: get a fuseholder and 7.5 amp automotive fuse and jump the cb (make sure the cb is in the open position) fuse blows you have a short somewhere it doesn't blow and you have a bad cb.
  10. Scoobyshep

    Help I got MEP-itis... It all started with just one

    I got my home generator right after a 9 day outage from hurricane Irma. Before that it seemed like every time the local squirrel population would expel flatulence the power would go out. Since install we have only had a couple of outages and they weren't any longer than a few hours. It's...
  11. Scoobyshep

    Help I got MEP-itis... It all started with just one

    they always start with one. For me it was a 004, which is now fully automated (HEY i was left unsupervised). That turned into sourcing one for a friend. then when covid hit I came across a 003 cheap. Now i have another friend wanting a set so back to the auctions I go.
  12. Scoobyshep

    MEP004A DC Circuit Interrupt trip issue

    I have never seen it but there is alot of people having issues with the noise suppressor (add on part on the pump) shorting. I believe they can be removed. There should be in the wire going to the pumps a black round rubber block. That os a disconnect. If you unplug that place the run...
  13. Scoobyshep

    MEP004A DC Circuit Interrupt trip issue

    First do you have the manuals (click the TM link up above if you dont). can you follow a wiring diagram and use a volt meter? No fuel is from a float in the day tank, so if the pumps are inoperative that may be an accurate fault. need to follow the diagram and see where you are loosing...
  14. Scoobyshep

    MEP-802A Popping CB1 as Soon as the Unit is Switched to Pump/Prime

    They are supposed to all ve wired the same and per the schematics. But since this is reality and not fantasy, the drawings are more of guidelines
  15. Scoobyshep

    MEP-003A Blower Wheel -- Requesting Removal Advice

    Youre welcome, I have never done on this exact thing but i did use this method to remove a lovejoy from an electric motor. Acetylene will work, be careful not to go too nutso on it. The last time i did something like this it was a mapp gas plumbers torch. keep the heat in ckeck and keep...
  16. Scoobyshep

    MEP-003A Blower Wheel -- Requesting Removal Advice

    I personally use a product by CRC called Knocker loose. Works very well on seized parts. Disclaimer: I have never actually pulled a blower on a 003, But the concept is about the same, I load the puller, heat the hub around the shaft and tap with a hammer as the puller loosens tighten it...
  17. Scoobyshep

    802a Connection corrosion

    Its more for aluminum wire, But NOALOX works well for preventing future corrosion. beware though, NOALOX is attracted to clean clothing and you will need a young priest and an old priest to clean it off.
  18. Scoobyshep

    802a Connection corrosion

    deoxit or corrosionex
  19. Scoobyshep

    reverse power?

    It is only for paralleling sets, Its an anti motorizing thing (basically the parallel set is driving harder than this set so its no longer generating power and is basically now an electric motor turning a diesel engine.
  20. Scoobyshep

    Mep-003a oil usage

    Rocksalt usually delevered by a shotgun