If you are isolating the main breaker for each panel with an interlock there should be no problem. What can get you into some trouble is if the grounding and bonding is not done correctly, especially if for some reason you run 1 panel on generator and the other on utility.
You also need to...
We have some big DC equipment at work, 24 and 48 vdc. Fun part is all the battery chargers are 24 vdc. The battery disconnects and jumpers are all anderson connectors and when you pull the disconnects the jumpers (think a plate with several connectors) the mating connector on the charger can...
short circuit will trip cb2
undervolt, underfrequency, reverse power, overload, permissive parallel will trip cb2 but are bypassable with battle short
low fuel, water temp, oil pressure, overvolt will kill the engine which also trips cb2
Engine speed is for frequency(Hz) only. The knob is for voltage only. What voltage are you reading?
If you are using the control cube to meter make sure the selector switch is in the right place. If you are reading voltage on an external meter and the knob does nothing, the first thing i...
One thing I have done to pots when they act funny, with the set off crank the pot all the way up and back down several times. sometimes the wiper gets corroded and needs a degunking. If its an open pot (you can see the wiper) a little deoxit goes a long way
Another thing is how you hook this up. depending on your connection changes how your bond (connection between ground and neutral) must be setup.
Before I go into a huge post about the differences and rules of grounding and bonding, How are you hooking up to your service?
And yes...