  1. K

    MEP-831A Oil Pressure Sender Suggestions

    Looking for suggestions for a oil pressure sender (not a switch) for a MEP-831A. 1/8 NPT, reasonably priced, with either a nut/bolt terminal or spade connection. Resistance of sender not critical.
  2. K

    MEP 831A vs MEP 701A

    I have a contact in TX that has about 100 of them available. PM me if interested and I'll send you his contact info.
  3. K

    MEP803a tripping overload fault while other unit chugs along no problems.

    The readings across CT3, K8-2 to K8-4 & R12 are all suspect. Those voltages are all above the 100% load level. In the 120/240 single phase setting R13 is connected in parallel to R12 via S8. Looks like possible a wiring issue to/from R13 and/or S8-14 & S8-13, bad contact closure between S8-13 &...
  4. K

    MEP803a tripping overload fault while other unit chugs along no problems.

    If the resistance of R10, R11, & R12 check out good then I'd recommend checking the AC voltage across each resistor when running the set under your load. At 100% load the voltages across R10, R11 & R12 should be ~5.6 VAC. At 133% load the voltages across R10, R11 & R12 should be ~7.5 VAC. If...
  5. K

    802 oil pressure switch. This is a Gov auction set

    Guy, I think you were looking at the HT switch and not the OP switch. Here is what the TM has for OP switch connections. 143C to C 126A to NC That's how my 802 is wired.
  6. K

    MEP 802 Shunt wires cut

    I suspect the set was giving them trouble and they chopped that section of wire harness out to make the set completely inoperable and not easily repaired. Probably then got a replacement genset.
  7. K

    MEP-803A Alternator Issues?

    Also check for chaffed battery cables. One battery being drained could be caused by one of the cables shorting to ground.
  8. K

    MEP 802 Shunt wires cut

    I think you have a typo. Should be ... Left side 112B, 112A on large terminal 159A on small screw Right side 109J, 109K on large terminal 158A on small screw The shunt is just a very low resistance high current resistor. Current passes thru it when the battery is either charging or...
  9. K

    802 oil pressure switch. This is a Gov auction set

    Here is how my 802A switch is wired.
  10. K

    MEP802 alternator and pulley missing

    Numerous dimensions here--> http://www.parttarget.com/3020-01-382-8782_3020013828782_88-20003.html
  11. K

    MEP802 alternator and pulley missing

    https://www.steelsoldiers.com/showthread.php?133229-dc-alternator-mep803a-need-part-number-for-the-pulley http://www.southernautomotive.com/catalog/product_info.php/products_id/1006
  12. K

    MEP-802/803/831 Generator Control & Parameter Monitor by WIFI Demo

    Will do. Taking a break from work on it for Thanksgiving. House full of company for the holiday. Fixing issues uncovered during beta testing by some beta testers. Added a data logging feature to capture historical parameters, Min, Max Average of each as well as total generator run time...
  13. K

    synchronizer for MEP-803A

    That was my solution at home except I utilize a 5K UPS (pure sine) coupled with my 17.7 KW solar battery bank. Picked up a couple of 5K UPS's for a song a few years back so the 2nd one is a backup. APC Matrix 5000's. 5K is more that adequate for running essentials during an outage for us. It's...
  14. K

    Mep-804a power output problems

    Do you really mean K1 or possibly K15 or K16 or some other relay?
  15. K

    MEP-831A - Generator Head Swap?

    It seems they aren't needed now. According to profo in post #23 the 831 is J609B compliant and the Northern Tools 4.5K is a direct bolt up. Thank you kindly for the offer though.
  16. K

    MEP-831A - Generator Head Swap?

    profo, A few pics would be awesome!
  17. K

    MEP-831A - Generator Head Swap?

    I'd be game but before we go down that road we need to verify that the engine is J609B compatible. Need someone to verify the bolt circle diameter on the 831 as well as the output shaft dimensions.
  18. K

    MEP-831A - Generator Head Swap?

    According to the TM the PMA provides 32-50 VAC to the Battery Charger. Sending 120 VAC into it would probably let the magic "white smoke" out of it.
  19. K

    MEP-831A - Generator Head Swap?

    Great info. I agree it's looking like a J609B bolt pattern. Any chance you can measure the distance from the mounting surface on the engine to the beginning of the shaft taper and also from the mounting surface on the engine to the end of the shaft? Also can you measure the bolt circle diameter...
  20. K

    MEP-831A - Generator Head Swap?

    Before we get too excited we need to verify if the 831's engine is a J609A, J609B or some other mounting pattern and shaft setup.