  1. K

    MEP-831A - Generator Head Swap?

    One easy way is with my governor controller. I can easily change the firmware to make the 831 run at the correct RPM based on the frequency output of the new gen head instead of the frequency output of the PMA. Simple firmware change.
  2. K

    MEP-803a - Field Flash Grinding Noise

    Just checked. I get 7.5 vdc at A1-6 with S1 in Start position. Guy did indicate the voltage out of R14 will be less than 24 volts, a change from what he posted earlier in the thread.
  3. K

    MEP-803a - Field Flash Grinding Noise

    Just checked using my 802. I get 8.5 VDC while holding S1 in the START position. Do you get any HZ or AC voltage reading on the panel meters with S1 in the START position? Is S6 set correctly?
  4. K

    MEP-802/803/831 Generator Control & Parameter Monitor by WIFI Demo

    On demand start systems such as an Automatic Transfer Switch, charge controllers, etc can command it to start/stop using a 2 wire interface. A basic contact closure on the 2 wire interface commands to set to start. Opening the remote contact closure will cause the set to shut down. One could...
  5. K

    MEP-802/803/831 Generator Control & Parameter Monitor by WIFI Demo

    Beta testing uncovered a few areas needing improvement. Thank you Beta testers! Installation & Users Manual updated to facilitate installation, wire harness changes, firmware improvements, & a PCB correction to fix a PCB routing error. New PCB's almost completed fab to roll in design updates...
  6. K

    MEP-831a Troubleshooting

    Sounds like unit A may have a bad controller if adjusting Stability & Gain don't do anything. The VAC across terminals A & B on the controller should be ~176 VAC, or approximately 254 Hz (3050 rpm) at no load when adjusted properly. Correct, my controllers have no adjustments. Just install...
  7. K

    Mep 803a Fuel Issue

    You might want to disconnect the outlet from the fuel pump and see what the flow is like. Did you replace the filter on the inlet to the pump? It may be clogged.
  8. K

    Need Parts Source: MEP 831a

    I have replacements for the SLC100 in stock. I also have a new SLC100 controller from Governors America Corp. Shoot me a PM if interested in either.
  9. K

    MEP-831a Troubleshooting

    K12 LED on indicates the 831's fault system detected a fault and removed power from the Governor Controller and hence the actuator resulting in low RPM. Without power to the actuator the voltage at H-J will be 0 VDC. Resetting the power switch clears the fault restoring power to the Governor...
  10. K

    Mep-803a no crank

    Glad to help :-)
  11. K

    MEP-831a Troubleshooting

    When it's at a low RPM and won't respond to a STOP is the LED in the K12 relay illuminated? When illuminated it indicates there is a Fault and power has been removed from the A5 Governor Controller. When this happens using the E-Stop or Run/STOP switch will have no affect on shutting down the...
  12. K

    Mep-803a no crank

    The C57400 (AKA version 2, blue square body plastic) switch only needs 1 jumper. It's black plastic covered and normally between terminals 4 & 8. It's part of the C57400 configuration. Internally the switch terminals 2 & 6 are connected to either 4 or 8 so with the one jumper terminals 2,4,6,8...
  13. K

    Mep-803a no crank

    novaman, PM sent regarding the manual
  14. K

    Mep-803a new to me

    Also verify it has the Quad Mod installed. Look for a fuse & fuse holder immediately to the left of the A1 Voltage Regulator inside the control cube.
  15. K

    MEP-831a Troubleshooting

    I assume when you measured ~202 Hz was the engine RPM much lower? When it stops responding to STOP is the engine RPM kinda low or still at a high RPM? Are there any Fault lights on when it stops responding to STOP? The Low Fuel fault is normally due to the fuel tank being virtually empty (or...
  16. K

    MEP-802/803/831 Generator Control & Parameter Monitor by WIFI Demo

    Interesting suggestions. Certainly not hard to incorporate into the software since it's aware of anytime the genset is inactive and run time..
  17. K

    MEP-802/803/831 Generator Control & Parameter Monitor by WIFI Demo

    Jiga... Thx for the offer. Many members offered to help.:-P Can only provide units to a few for beta testing. First beta test unit sent out last week to a S.S. member. Second unit going out this week to another S.S. member. Will need to gather results from beta testing and roll in any needed...
  18. K

    MEP-831a Troubleshooting

    I'd suggest disconnecting terminals F & G from the Governor Controllers. This removes power from the governor controller. Be sure they do not touch each other or anything else. Lift the actuator arm off the magnet. Start the generator and see what Hz/RPM reading you get. If you have a high RPM...
  19. K

    831a Starter Issues

    If K2 is "clunking then the TVS diode is not an issue. Should be fine to jump +24 volts to K2A2.